Remote Area Power Systems
Generator Interactive Inverters provide mains quality power efficiently
and automatically. The system uses batteries to store energy for periods
when power demand is low, and automatically starts a diesel generator
set when demand is high or when the batteries require recharging.
This mode of operation ensures that the diesel fuel is efficently converted
to electricity by only running the generator at medium to heavy loads and
only for a small proportion of the day. Power is drawn from the batteries
and converted to a mains quality sine wave by a microprocessor controlled
inverter. While the generator is operating, it supplies power to the load
and the inverter charges the batteries. However if heavy loads occur, both
the inverter and the generator can supply the load, giving a peak capacity
equal to the sum of the inverter and the generator ratings. This allows
smaller generators to be used compared to inverter charger systems.
An alphanumeric LCD display allows inverter variables to be displayed and
allows suitably qualified technicians to adjust operating parameters to
optimise system performance.This is a worked example, showing how to set
up the parameters of a RAPS inverter for a solar-diesel remote power system.
It was prepared by the Renewable Energy Centre at the Brisbane North Institute
of TAFE, as part of their Hybrid Energy Systems course.
3 - 5 kW RAPS Specifications
Common to all units:
- Automatic Bypass: Supply is maintained by the generator if the inverter
is off line.
- Data Logging Remote Access: RS232 port, standard data logging and
remote access via modem, satellite, GSM and CDMA technology.
- Cooling: Convection and thermostatically controlled fans.
- Enclosures: Electronics IP50, transformer and heatsink IP23. Weatherproof
enclosures or rack mounting are available on request.
- Protection: Over current trip, over voltage, over temperature, reverse
polarity, fast electronic trip, transient over voltage protection.*
AC output voltages of 110, 120, 220 and 230 are available on application.
* Other DC voltages between 24 VDC and 120 VDC are available on application.
| Model |
RAP-3-24-1 |
RAP-3-48-1 |
RAP-5-48 |
RAP-5-110 |
RAP-5-120 |
| PDF of Brochures of items |
 |
| Input voltages |
24 VDC |
48 VDC |
48 VDC |
110 VDC |
120 VDC |
| Output voltage & frequency* |
240 Vac
50 or 60 Hz |
240 Vac
50 or 60 Hz |
240 Vac
50 or 60 Hz |
240 Vac
50 or 60 Hz |
240 Vac
50 or 60 Hz |
| Continuous output @ 40°C |
2.7 kW |
3 kW |
5 kW |
5 kW |
5 kW |
| 1 hour rating @ 40°C |
3.2 kW |
3.6 kW |
6 kW |
6 kW |
6 kW |
| ½ hour rating @ 40°C |
3.5 kW |
3.9 kW |
6.5 kW |
6.5 kW |
6.5 kW |
| Surge rating |
5.4 kW |
6 kW |
10 kW |
10 kW |
10 kW |
| Maximum charge current |
90 A |
35 A |
83 A |
35 A |
35 A |
| Peak efficiency |
> 90 % |
> 92 % |
> 92 % |
> 94 % |
> 94 % |
| Power factor range |
0 - 1 |
0 - 1 |
0 - 1 |
0 - 1 |
0 - 1 |
| Idle power |
35 W |
35 W |
50 W |
50 W |
50 W |
| Standby power |
< 10 W |
< 10 W |
< 10 W |
< 10 W |
< 10 W |
| Integrated isolation AC/DC |
cct breaker |
cct breaker |
cct breaker |
cct breaker |
cct breaker |
| Indicators |
LED & LCD |
LED & LCD |
LED & LCD |
LED & LCD |
LED & LCD |
| Inverter mass |
60 kg |
60 kg |
70 kg |
70 kg |
70 kg |
| Data logging |
Yes |
Yes |
Yes |
Yes |
Yes |
| Internal Gen contactor |
6 kVA |
6 kVA |
10 kVA |
10 kVA |
10 kVA |
| External Gen contactor |
optional |
optional |
optional |
optional |
optional |
| Remote access |
RS232 |
RS232 |
RS232 |
RS232 |
RS232 |
15 - 40 kW 3 PhaseRAPS Specifications
Common to all units:
- Automatic Bypass: Supply is maintained by the generator if the inverter
is off line.
- Data Logging Remote Access: Standard data logging and remote access
via modem, satellite, GSM and CDMA technology.
- Cooling: Convection and thermostatically controlled fans.
- Enclosures: Electronics IP50, transformer and heatsink IP23. Weatherproof
enclosures or rack mounting are available on request.
- Protection: Over current trip, over voltage, over temperature, reverse
polarity, fast electronic trip, transient over voltage protection
| Model |
RAP-10-108
RAP-10-120 |
RAP-12-108
RAP-12-120 |
RAP-15-120 |
| PDF of Brochures of items |
 |
| Input voltages |
108 / 120 VDC |
108 / 120 VDC |
120 VDC |
| Output voltage & frequency* |
240 Vac
50 or 60 Hz |
240 Vac
50 or 60 Hz |
240 Vac
50 or 60 Hz |
| Continuous output @ 40°C |
10 kW |
12 kW |
15 kW |
| 1 hour rating @ 40°C |
12 kW |
14 kW |
18 kW |
| ½ hour rating @ 40°C |
13 kW |
15.6 kW |
19.5 kW |
| Surge rating |
22 kW |
22 kW |
30 kW |
| Maximum charge current |
70 A |
80 A |
100 A |
| Peak efficiency |
> 94 % |
> 93 % |
> 93 % |
| Power factor range |
0 - 1 |
0 - 1 |
0 - 1 |
| Idle power |
100 W |
120 W |
150 W |
| Standby power |
30 W |
30 W |
30 W |
| Autostart on demand |
Yes |
Yes |
Yes |
| Mimimum start load |
12 - 15 W |
12 - 15 W |
12 - 15 W |
| Integrated isolation AC/DC |
cct breaker |
cct breaker |
cct breaker |
| Indicators |
LED & LCD |
LED & LCD |
LED & LCD |
| Inverter mass |
260 kg |
260 kg |
280 kg |
| Cooling system |
5 fans |
5 fans |
5 fans |
| Data logging |
Yes |
Yes |
Yes |
| Internal DC cct breaker |
Yes |
Yes |
Yes |
| Internal Gen contactor |
20 kVA |
20 kVA |
20 kVA |
| Remote access |
RS232 |
RS232 |
RS232 |
15 - 40 kW 3 Phase RAPS Specifications
Common to all units:
- Automatic Bypass: Supply is maintained by the generator if the inverter is off line.
- Low distortion, high power load presented to generator during charging for best generator performance.
- All units available in 220 / 230 / 240 VAC 50 or 60 Hz output (240 / 415, 230 / 380V three phase plus neutral connection). 120 / 208 VAC on application.
- Data Logging Remote Access: RS232 port, standard data logging and remote access via modem, satellite, GSM and CDMA technology.
- Cooling: Convection and thermostatically controlled fans.
- Enclosures: Electronics IP50, transformer and heatsink IP23. Weatherproof enclosures or rack mounting are available on request.
- Protection: Over current trip, over voltage, over temperature, reverse polarity, fast electronic trip, transient over voltage protection
| Model |
RAP-15-48 |
RAP-15-108
RAP-15-120 |
RAP-20-108
RAP-20-120 |
RAP-25-108
RAP-25-120 |
RAP-30-108
RAP-30-120 |
RAP-40-120 |
| PDF of Brochures of items |
 |
| Input voltages |
48 VDC |
108/120 VDC |
108/120 VDC |
108/120 VDC |
108/120 VDC |
120 VDC |
| Operating DC voltage range |
42-62 V |
100-158 V |
100-158 V |
100-158 V |
100-158 V |
100-158 V |
| Continuous output @ 40°C |
15 kW |
15 kW |
20 kW |
25 kW |
30 kW |
40 kW |
| 1 hour rating @ 40°C |
18 kW |
18 kW |
24 kW |
30 kW |
36 kW |
48 kW |
| ½ hour rating @ 40°C |
19.5 kW |
19.5 kW |
26 kW |
32.5 kW |
39 kW |
52 kW |
| Surge rating |
30 kW |
30 kW |
40 kW |
50 kW |
60 kW |
80 kW |
| Maximum charge current |
250 A |
120 A |
150 A |
200 A |
250 A |
300 A |
| Peak efficiency |
> 91 % |
> 93 % |
> 93 % |
> 93 % |
> 93 % |
> 93 % |
| Power factor range |
0 - 1 |
0 - 1 |
0 - 1 |
0 - 1 |
0 - 1 |
0 - 1 |
| Idle power |
< 150 W |
< 150 W |
< 200 W |
< 250 W |
< 300W |
< 400W |
| Integrated isolation AC/DC |
cct breaker |
cct breaker |
cct breaker |
cct breaker |
cct breaker |
cct breaker |
| Indicators |
LED & LCD |
LED & LCD |
LED & LCD |
LED & LCD |
LED & LCD |
LED & LCD |
| Inverter mass |
210 kg |
290 kg |
310 kg |
330 kg |
350 kg |
390 kg |
| Internal Gen contactor |
no |
< 30 kVA |
< 30 kVA |
no |
no |
no |
| External Gen contactor |
required |
optional |
optional |
required |
required |
required |
Standards:
All inverters are designed to AS3100 / AS2604 / AS61000.3.5 and the draft AS/NZ
standard for grid connect inverters.
Low distortion, high power presented to to generator during charging for best
generator performance.
Refer to sales staff for details of applicable compliance testing.
|